Planning the electrical installation
53
3ADW000462R0401 DCS880 Hardware manual e d
Converters size H1 ... H3 as large field exciter
Wiring the drive according to this diagram offers the highest degree of monitoring functions done by
the drive.
PE
+ -
L1
K1
T2
690 V
660 V
600 V
575 V
525 V
500 V
450 V
415 V
400 V
380 V
115 V
230 V
K16
K16
XSMC:1
XSMC:2
F7
F2
1
2
SDCS-CON-H01
J6
AI1 - J1 AI2 - J2 AO1 - J5
SF_880_042_DCS_ans-large field exc_a.ai
D2D - J3
current 20 mA
voltage 10 V
default
default
default
default
open
terminated
open
closed
default
Slot3
Slot2
Slot1
Control panel
DCSLink
Mains
contactor
Reset
Off2 (current off)
Overvoltage
protection trigger
OUT1
SGND
IN1
IN2
NC
COM
NO
NC
COM
NO
NC
COM
NO
COM
NO
COM
NO
B
A
BGND
DI1
DI2
DIO1
DIO2
DI3
DI4
DI5
DI6
+10V
-10V
AGND
AI1-
AI2+
AI2-
AI1+
DICOM
+24VD
DIOGND
+24VD
DIL
AO2
AGND
AGND
AO1
AI3-
AI3+
1 2 3 4
XRO1
XSMC
1211 2221 2313
3421
XRO2
X13 X200
3231 33
XRO3
XSTO
XDIO 1
XD2D
132
XAI
12
345 67
XDI
12 34 562
XAO
1234
IACT
5
XD24 1 2 3 4 5
89
OnBoard
tacho feedback
Overvoltage
protection
OnBoard Encoder Feedback
U1
DCF506
V1
W1
D1C1
-
+
1 2
XAUX (X99)
3
4
K1
L1 L2 L3
15
26
Power
supply
F5
1
2
1
max.
±270 V
7
EGND
24 V 5 V
8
J4D
1 2 3 4 5 6
2
XENC
+ A - + B - + Z -
1
2
OFF2
OFF2
1
2
X14:1
X14:2
K8
Aux supplyMains
L1 L2
3
4
1
2
d Disabled by parameter or not selected (plus code +0S163).
X200
X53 1
Control from
armature converter
22
J1
GNDB
13
X52 3
F100 ... F102
Field exciter
X10 F+X14 1 2
To DI5
X12 X11 F-
c K1 can also be controlled by the armature converter.
If the installation is not equipped with K1 and the
conver is direct supplied from a high voltage
transformer an additional overvoltage protection
(capacitors) is required.
c
d
c
SDCS-PIN-H01
F1
To OVP
SDCS-DSL-H10
J4
A B C
J4
D
Encoder
supply
10 k 24 V
5 V
120
pull up
differential