Planning the electrical installation
58
3ADW000462R0401 DCS880 Hardware manual e d
Fan data for DCS880 (H5 ... H8)
The fan needs an input voltage of 400 V
AC
at 50 Hz. For 460 V
AC
/500 V
AC
use autotransformer
(T8).
The fan needs an input voltage of 460 V
AC
at 60 Hz. For 500 V
AC
use autotransformer (T8).
Fan connection for DCS880 (H5 ... H8)
Fan R2E250-RB GR28C-2DK GR35C-2DD
Rated voltage [V
AC
] 230; 1~ 400
500
460 400 / 460 /
500 V
460 /
500 V
Tolerance [%] ±10 ±10 ±10 ±10
Frequency [Hz] 50 60 50 60 50 60
Power consumption [W] 227 390 660
600
1100 2100 3000
Current consumption [A] 1.1 1.7 1.4
0.8
1.8 4.0 5.3
Blocking current [A] 3.1 3.1 at 400 V 8.0
at 500 V 2.8
at 460 V 8.0 at 400 V > 17 at 460 V > 15
Air flow [m
3
/h]
at working point
800
1.0 A
850
1.6 A
1600 @ 1.2 A
(400 V )
1500 @ 0.7 A
(500 V )
1700 @ 1.6 A
(460 V )
4000 @ 4 A
(400 V)
4500 @ 5.3 A
(400 V)
Max. ambient temperature [°C] < 55 < 55
Useful lifetime of grease appr. 40,000 h/40°C appr. 30,000 h/40°C
Protection internal Temperature detector: U
N
230 V~; I
N
2.5 A~
Converter housing
Configuration 5
H5, H6
Configuration 6
H7
Configuration 7
H8
U1 V1 W1 U2 V2 W2 TK TKPE
at
U1-W2
V1-U2
W1-V2
M
~
J
U1 V1 W1U2 V2W2PE TB TB
at
M
~
U1 V1 W1U2 V2W2PE TB TB
at
U2 - V2 - W2
M
~
U1-W2
V1-U2
W1-V2
M
~
231X2:
4 5
LN
SA_880_011_DCS_FAN_b.ai
Connection
Connection
Connection