EasyManua.ls Logo

ABB DCS880 series - Pulse Encoder Connection Principles

ABB DCS880 series
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical installation
70
3ADW000462R0401 DCS880 Hardware manual e d
Pulse encoder connection principles
Two different encoder connections are available.
1. Differential connection; only pulse encoders generating voltage signals can be used.
2. Single-ended (push pull) connection; only pulse encoders generating voltage signals can be used.
Pulse encoder connection principles:
In case of single ended encoders jumpers J4A ... J4C have to be set to a neutral position according
to the table below.
To get a threshold lower than 5 V each terminal XENC:1, 3 and 5 must be connected via a resistor R
to GND.
1k0 4k7
1k0 4k7
+5V
121
W
100 nF
10k
+5V
0V
+5V or +24V
3
2
1
J4A
R
2k2
SS_880_005_encoder_b.ai
XENC:1
XENC:2
XENC:7
XENC:8
ENCODER CHANNEL A
Single ended
open collector
SDCS-CON-H01 ENCODER INPUT A
2k2
1k0 4k7
1k0 4k7
+5V
121
W
100 nF
10k
+5V
0V
+5V or +24V
XENC:1
XENC:2
XENC:7
XENC:8
3
2
1
J4A
R
SS_880_005_encoder_b.ai
ENCODER CHANNEL A
Single ended
push pull
SDCS-CON-H01 ENCODER INPUT A
Jumper settings for single ended encoders connected to SDCS-CON-H01
Jumper SDCS-CON-H01
J4A
J4B
J4C
2 - 3
5 - 6
8 - 9
2 - 3
5 - 6
8 - 9
Single ended
J4D 5 V: 10 - 11 24 V: 11 - 12 Voltage source

Table of Contents

Other manuals for ABB DCS880 series

Related product manuals