ABB i-bus
®
KNX
Parameters
364 2CDC508198D0211 Rev. A | AC/S 1.x.1
Object name
Object type
Unit
COV send
condition
Cooling distribution circuit: Control On/Off override disable/enable
Binary value
-
-
The module has this BACnet output object in the following conditions:
If the Yes option is selected for the Supply temperature control parameter and the Yes option is selected for the
Enable
cooling circuit control based on ASM input socket parameter.
If the Yes option is selected for the Switch off if no room demand
parameter.
Outputs whether the control (Off/On) for the cooling distribution circuit controller has been overridden via the web user
interface.
Signal value: 0 = Not overridden
1 = Overridden
Cooling distribution circuit: Room control values
Analog value
% (98)
1.0
The module has this BACnet output object if the Yes option is selected for the Switch off if no room demand parameter.
Outputs the highest room setpoint temperature that is present on the ASM input socket and that is used by the Economy mode
and Switch off if no room demand functions.
Signal value:
0…100 %
Cooling distribution circuit: Pump A override disable/enable Binary value - -
The module has this BACnet output object if the Yes option is selected for the Override by WebUI parameter.
Outputs whether the pump for the cooling distribution circuit is overridden.
Signal value:
0 = Disabled
1 = Enabled
Cooling distribution circuit: Pump A override value
Binary value
-
-
The module has this BACnet output object if the
Yes
option is selected for the
Override by WebUI
parameter.
This object specifies the state with which the pump for the cooling distribution circuit is overridden if the pump override is
active.
Signal value:
0 = Off
1 = On