ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 365
condition
Cooling distribution circuit: Pump A operating status (Off/On)
The module has this BACnet output object if the Yes option is selected for the Pump display operating status parameter.
Outputs the operating status (Off/On) provided by the pump. On pumps with their own control, this operating status can differ
from the operating status of the cooling distribution circuit controller.
Signal value: 0 = Inactive
1 = Active
Cooling distribution circuit: Pump A relay status Binary value - -
Outputs the status of the cooling distribution circuit controller's pump.
1 = On
Cooling distribution circuit: Pump A fault
The module has this BACnet output object if the Yes option is selected for the Pump display pump fault status parameter.
Outputs the fault status provided by the pump.
1 = Active
Cooling distribution circuit: Pump A repair switch status
The module has this BACnet output object if the Yes option is selected for the Display pump repair switch status parameter.
Outputs the contact position provided by the pump repair switch.
1 = Active
Cooling distribution circuit: Pump B override disable/enable
The module has this BACnet output object if the Yes option is selected for the Double pump parameter and the Yes option is
selected for the Override by WebUI parameter.
Outputs whether the second pump for the cooling distribution circuit is overridden.
Signal value: 0 = Disabled
1 = Enabled