ABB i-bus
®
KNX
Parameters
366 2CDC508198D0211 Rev. A | AC/S 1.x.1
condition
Cooling distribution circuit: Pump B override value
The module has this BACnet output object if the Yes option is selected for the Double pump parameter and the Yes option is
selected for the Override by WebUI parameter.
This object specifies the state with which the second pump for the cooling distribution circuit is overridden if the pump override
is active.
1 = On
Cooling distribution circuit: Pump B Operating Status (Off/On)
The module has this BACnet output object if the Yes option is selected for the Double pump parameter and the Yes option is
selected for the Pump display operating status parameter.
Outputs the operating status (Off/On) provided by the second pump. On pumps with their own control, this operating status
can differ from the operating status of the cooling distribution circuit controller.
1 = Active
Cooling distribution circuit: Pump B relay status
The module has this BACnet output object if the Yes option is selected for the Double pump parameter.
Outputs the status of the second pump from the cooling distribution circuit controller.
Signal value: 0 = Off
1 = On
Cooling distribution circuit: Pump B fault
The module has this BACnet output object if the Yes option is selected for the Double pump parameter and the Yes option is
selected for the Pump display pump fault status parameter.
Outputs the fault status provided by the second pump.
1 = Active