ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 367
condition
Cooling distribution circuit: Pump B repair switch status
The module has this BACnet output object if the Yes option is selected for the Double pump parameter and the Yes option is
selected for the Display pump repair switch status parameter.
Outputs the contact position provided by the second pump repair switch.
Signal value: 0 = Inactive
1 = Active
Cooling distribution circuit: Valve control value Analog value % (98) 1.0
The module has this BACnet output object
if the 3-way valve (mixing valve) option or the 2-way valve option is selected for the
Valve type parameter.
Outputs the valve control value for the cooling distribution circuit. This value is received from the cooling distribution circuit
controller linked via the related module group object.
Signal value: 0…100%
Cooling distribution circuit: Valve override disable/enable
The module has this BACnet output object if the 3-way valve (mixing valve) option or the 2-way valve option is selected for the
Valve type parameter and the Yes option is selected for the Valve override disable/enable
parameter.
Outputs whether the override of the cooling distribution circuit's valve is active or inactive.
Signal value: 0 = Disabled
1 = Enabled
Cooling distribution circuit: Valve override control value
The module has this BACnet output object if the
3-way valve (mixing valve)
2-way valve
option is selected for the
Valve type parameter and the Yes option is selected for the Valve override disable/enable parameter.
Outputs the value used to override the cooling distribution circuit's valve if the override is active.
Cooling distribution circuit: Status Valve purge
The module has this BACnet output object if the
3-way valve (mixing valve)
2-way valve
option is selected for the
Valve type parameter and the Yes option is selected for the Status Valve purge parameter.
Outputs the status as to whether the cooling distribution circuit controller is actually undertaking a valve purge. This value is
received from the cooling distribution circuit controller linked via the related module group object.
Signal value: 0 = Inactive
1 = Active