Required equipment
NoteEquipment
30, Type B (ABB F202 B-16/0.03
or equal residual current circuit
breaker.)
External earth fault protection (residual current device,
RCD)
See Standard toolkit for controller
on page 202.
Standard toolkit
Circuit diagram - OmniCore E10,
3HAC076810-008
Circuit diagram
Line fusing
There is no integrated fuse inside the OmniCore E10 controller. An external fuse
or circuit breaker must be added by the integrator, according to the full load current
rating. See Load current on page 38.
Connecting the power
The following procedure describes how to connect the main power to the controller.
CAUTION
Always inspect the connector for dirt or damage before connecting it to the
controller. Clean or replace any damaged parts.
Action
Connect the main power cable to the power inlet connector X0 and lock it by
pressing the locking levers.
Tip
When you hear a clear clicking sound, it is locked.
1
74 Product manual - OmniCore E10
3HAC079399-001 Revision: C
© Copyright 2019-2022 ABB. All rights reserved.
3 Installation and commissioning
3.5.5 Connecting power supply to and grounding the controller
Continued