xx2100001309
PWR_DO224V_IO_EXT1
GND_DO40V_IO_EXT3
DO46DO85
DO38DO77
DO210DO69
DO112DO511
0V_IO_EXT140V_IO_EXT13
GND_DI16GND_DI15
DI118DI1617
DI220DI1519
DI322DI1421
DI424DI1323
DI526DI1225
DI628DI1127
DI730DI1029
DI832DI931
The connectors contain 16 digital input signals, 8 digital output signals, 24 V and
0 V for the outputs, and 0 V for the inputs.
CAUTION
The process power supply(PWR_DO, GND_DO) should be supplied separately.
The 24V_IO_EXT rails must handle maximum output current of 4 A in total.
For connection details, see Circuit diagram - OmniCore E10, 3HAC076810-008.
Customer safety interface - X9
Note
The FlexPendant connector can only be used to connect a FlexPendant and
CANNOT be used to connect any other devices.
All external safety devices must be connected from the customer safety interface.