EasyManua.ls Logo

ABB RET670 - Page 148

ABB RET670
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-3U
0
=U
ref
Operate area
Instrument
transformer
angle error
3I
0
(prim)
3I
0
(to prot)
a
Characteristic after
angle compensation
RCAcomp
en06000651.vsd
RCADir = 0º
IEC06000651 V2 EN
Figure 61: Explanation of RCAcomp
Operation mode 3I
0
· 3U
0
· cosφ
Procedure
1. Set the polarizing voltage to 1.2 · UNRel> and the phase angle between
voltage and current to the set characteristic angle (RCADir), the current
lagging the voltage.
2. Measure that the operate power is equal to the SN> setting for the set
directional element.
Note that for operation, both the injected current and voltage must be greater
than the set values INRel> and UNRel> respectively.
The function activates the START and STDIRIN outputs.
3.
Measure with angles j = RCADir +/- 45° that the measuring element operates
when 3I
0
· 3U
0
· cos (RCADir - j) = 3I0 · 3U0 · cos(+/-45) = SN>.
4. Compare the result with the set value. Take the set characteristic into
consideration, see figure
60 and figure 61.
5.
Measure the operate time of the timer by injecting 1.2 · UNRel> and a current
to get two times the set SN> operate value.
Section 13 1MRK 504 088-UEN C
Verifying settings by secondary injection
142
Installation and commissioning manual

Table of Contents

Other manuals for ABB RET670

Related product manuals