2. DESPATCH AND STORAGE 15
2.4.4. Handling by hydraulic lift trolley
• Fasten a hydraulic lift trolley of suitable
capacity to each of the front and rear of the
panel (fig. 2.4.4.1) in accordance with the
manufacturer’s instructions.
Hazard warning
The high centre of gravity means there is
a high risk of tipping. Avoid jerky
motions!
—
Fig. 2.4.4.1:
Handling by hydraulic
lift trolley
2.5. Intermediate storage
• Store the panels in the upright position.
• Do not stack the panels.
• Protect the transport units from damage.
The conditions for optimum intermediate
storage without packaging or with basic
packaging are as follows:
• The storeroom must comply with the normal
operating conditions for the switchgear
installation (see IEC 62271-1).
• Cover the unpackaged panels with protective
sheeting, remembering to preserve sufficient
air circulation.
• Prevent condensation on the panels by partially
opening the packaging and heating the storage
room accordingly.
The conditions for optimum intermediate
storage with packaging and preservation are as
follows:
• Check the packaging for damage.
• Store the transport units in a dry place
protected from the weather.
• Contact us if
- the storage life of the preservation is
exceeded,
- the packaging with preservation is damaged.