1569‐PT060EE1 Rev.7 Page22of62
3.8 Connection of serial lines (side A)
T060Eisequippedwith2seriallines.
Output1,opto‐isolatedandconfigurableasRS485orRS232andoutput2foreseenfortheRS485interface.
Output2isdisabledincaseofPROFIBUSoption.
IncompliancewithEIAstandards,thecable’s
lengthmustnotexceed15metresincaseofRS232and1000metresin
caseofRS485.
RS232
Itissuggestedtouseashieldedcableandconnecttheshieldononesideonly.
RS485
Useatwistedshieldedcable(1couple)suitableforserialcommunications.
Useseparatetroughs
fromthoseofpowerlines,wherepossible.
INDICATION FUNCTION TERMINAL
+RS485/TX TXRS232(port1) 27
‐RS485/RX RXRS232(port1) 26
+RS485/TX RX485+(port1) 27
‐RS485/RX RX485+(port1) 26
SGND1 SignalGround 25
+RS485 RX485+(port2) 24
‐RS485 RX485‐ (port2) 23
SGND2 SignalGround 22
3128 29 30
-S
+R
-R
3432 33
+S
3635 37
-A
+A
3938
-R
+R
-S
+S
-A
+A
LOAD CELL 2 LOAD CELL 1
232019 2221 2524 2726
SGND 3
IOUT+
VOUT+
SGND 2
-RS485
+RS485
SGND 1
-RS485/RX
+RS485/TX
SERIAL
OUT 1
SERIAL
OUT 2
ANALOG
OUTPUT
OPTO OPTO