1569‐PT060EE1 Rev.7 Page24of62
3.10 Connection of relay outputs (side B)
Initsstandardversion,theinstrumentisequippedwithfive(5)SPSTrelayoutputs.
Foreachrelay,theuserboastsagenerallyopencontact(NA)notundervoltage.
Thecapacityofthecontactsis0.5Ato48V onresistiveload.
Iftherelaycontactsareusedtocontrolrelaycoils,arcsuppressiondevicesparalleltothecontactmustbeforeseen.
Useseparatetroughsfromthoseofpowerlines,wherepossible.
Therelaysaremanagedasalarmrelays,thereforetheyarealwayskeptenergizedandarede‐energizedincaseof
alarm.
INDICATION FUNCTION TERMINAL
OUT1 Relay1‐ NO 4
OUT1 Relay1‐ C 5
OUT2 Relay2‐ NO 6
OUT2 Relay2‐ C 7
OUT3 Relay3‐ NO 8
OUT3 Relay3‐ C 9
OUT4 Relay4‐ NO 10
OUT4 Relay4‐ C 11
OUT5 Relay5‐ NO 12
OUT5 Relay5‐ C 13
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
OUT 1
OUT 4
OUT 2
OUT 1
OUT 2
OUT 4
OUT 3
OUT 3
G SAFETY OUT
V SAFETY OUT
OUT 5
OUT 5
INP 2
INP 1
C INP
100-240VAC
1
24VAC 48VAC
LL
NN
EE
2
3
24VDC
-
+L
E
N