EasyManua.ls Logo

Advantech Adam-4013 RTD

Advantech Adam-4013 RTD
390 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
111 ADAM-4000 Series User Manual
Chapter 4 Command Set
Table 4.25: ADAM-4069 Command Table
Command Syntax Command Name Command Description Page No.
%AANNTTCCFF Configuration
Sets address, baud rate, and/or
checksum status, to a digital I/O mod-
ule
7-4
$AA6 Digital Data In
Returns the values of the digital I/O
channels of the addressed module
7-6
#AABB(data) Digital Data Out
Writes specified values to either a
single channel or all channels simul-
taneously
7-8
$AA2 Configuration Status
Returns the configuration parame-
ters of a specified digital I/O module
7-14
$AA5 Reset Status
Indicates whether a specified digital I/
O module was reset after the last time
the $AA5 command was issued
7-16
$AAF
Read Firmware
Version
Return the firmware version code
from the specified digital I/O module
7-18
$AAM Read Module Name
Return the module name from the
specified digital I/O module
7-19
$AAX0TTTTDD Write Safety Value
Force the DO channels to safety
status when communication is time-
out and over pre-defined period.
7-21
$AAX1 Read Safety Value
Read the time-out setting and pre-
defined safety status of DO channels.
7-22
$AAP
Read low power
status
The command requests the module
at address AA to return the low power
status of module
7-25
$AAS Set low power status
The command requests the module
at address AA to set and return the
low power mode of module
7-26