121 ADAM-4000 Series User Manual
Chapter 5 Analog Input Module Commands
Table 5.1: Input Range Codes (Type Codes)
Input Range Code (Hex) Input Range for 4011, 4011D, 4018, 4018+
(Thermocouple and ± 20 mA only), 4018M
00 ± 15 mV
01 ± 50 mV
02 ± 100 mV
03 ± 500 mV
04 ± 1 V
05 ± 2.5 V
06 ± 20 mA
07 4~20mA
0E Type J Thermocouple 0 ~ 760 °C
0F Type K Thermocouple 0 ~ 13700 °C
10 Type T Thermocouple -100 ~ 400 °C
11 Type E Thermocouple 0 ~ 1000 °C
12 Type R Thermocouple 500 ~ 1750 °C
13 Type S Thermocouple 500 ~ 1750 °C
14 Type B Thermocouple 500 ~ 1800 °C
Input Range Code(Hex) Input Range for 4012,4017,4017+
08 ± 10 V
09 ± 5 V
0A ± 1 V
0B ± 500 mV
0C ± 150 mV
0D ± 20 mA
07 4~20mA
Notice: The input range requires the usage of a 125 current conversion resistor
Input Rage Code (Hex) Input Range for 4016
00 ±15 mV
01 ±50 mV
02 ±100 mV
03 ±500 mV
06 ±20 mA
Input Range Code (Hex) Input Range for 4013
20 Platinum, -100 ~ 100 °C, a=0.00385
21 Platinum, 0 ~ 100 °C, a=0.00385
22 Platinum, 0 ~ 200 °C, a=0.00385
23 Platinum, 0 ~ 600 °C, a=0.00385
24 Platinum, -100 ~ 100 °C, a=0.003916
25 Platinum, 0 ~ 100 °C, a=0.003916
26 Platinum, 0 ~ 200 °C, a=0.003916
27 Platinum, 0 ~ 600 °C, a=0.003916
28 Nickel, -80 ~ 100 °C
29 Nickel, 0 ~ 100 °C

Table of Contents