Benchmark 1500 - 2000 Boilers
Installation, Operation & Maintenance Manual
OMM-0097_0E AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 1 of 182
GF-142 Ph.: 800-526-0288 10/01/2015
USER MANUAL
Installation, Operation and Maintenance
BENCHMARK
1500 and 2000
Gas-Fired Boilers
Natural Gas Modulating
& Condensing Hot Water
Boiler Models:
BMK 1500
BMK 2000
Applicable to Serial Numbers:
G-15-2700 and Above
Latest Update: 10/01/2015

Table of Contents

Questions and Answers

  • M
    Molly MckeeSep 3, 2025
    What should I do if my Aerco Boiler displays a Stepper Motor Failure?
    • S
      Seth StevensSep 4, 2025
      If your Aerco Boiler displays a Stepper Motor Failure, consider the following: * Air/Fuel Valve out of calibration: Refer to GF-112 (C-More O & M) and perform the Stepper Feedback Calibration procedure in Section 6, section 6.2.1. * Air/Fuel Valve unplugged: Check that the Air/Fuel Valve is connected to the Control Box. * Loose wiring connection to the stepper motor: Inspect for loose connections between the Air/Fuel Valve motor and the wiring harness. * Defective Air/Fuel Valve stepper motor: Replace stepper motor. * Defective Power Supply Board or fuse: Check DS1 & DS2 LEDs on Power Supply Board. If they are not steady ON, replace Power Supply Board. * Defective IGST Board: Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF every second. If not, replace IGST Board.
  • R
    Rebecca SchwartzSep 2, 2025
    What causes a High Gas Pressure fault in my Aerco Benchmark 2000?
    • L
      Lori HarrisSep 3, 2025
      A High Gas Pressure fault in your Aerco Boiler may be due to: * Incorrect supply gas pressure: Check to ensure gas pressure at inlet of SSOV does not exceed 14” W.C. * Defective SSOV Actuator: If gas supply pressure downstream of SSOV Actuator cannot be lowered to the range of 3.6” ± 0.2” W.C. for BMK1500 or 3.9” ± 0.2” W.C. for BMK2000 using the gas pressure adjustment screw (see section 4.3.1 or 4.3.2, step 10), the SSOV Actuator may be defective. * Defective High Gas Pressure Switch: Remove the leads from the high gas pressure switch. Measure continuity across the common (C) and normally closed (NC) terminals with the unit not firing. Replace the switch if continuity does not exist.
  • D
    Douglas SimpsonSep 2, 2025
    Why is my Aerco Benchmark 2000 showing a Low Gas Pressure error?
    • E
      egonzalezSep 2, 2025
      A Low Gas Pressure error in your Aerco Boiler can occur due to: * Incorrect supply gas pressure: Measure gas pressure upstream of the SSOV Actuator(s) with the unit firing. For FM gas trains, ensure it is between 6.0” W.C. and 14” W.C. For DBB gas trains, ensure it is between 6.5" W.C. and 14” W.C. * Defective Low Pressure Gas Switch: Measure gas pressure at the low gas pressure switch. If it is greater than 4.7” W.C. (for both BMK 1500 and BMK 2000), measure continuity across the switch and replace if necessary.
  • M
    medinalarryAug 27, 2025
    What causes a Delayed Interlock Open error on my Aerco Benchmark 2000 Boiler?
    • C
      Craig VazquezAug 27, 2025
      A Delayed Interlock Open error on your Aerco Boiler can be caused by a Delayed Interlock Jumper not properly installed or missing. Check to ensure the jumper is properly installed across the delayed interlock terminals in the I/O Box. Alternatively, it could be caused by a device proving switch hooked to interlocks that is not closed. If there are 2 external wires on these terminals, check to see if an end switch for a proving device (such as a pump, louver, etc.) is tied to these interlocks. Ensure that the device and/or its end switch is functional. A jumper may be temporarily installed to test the interlock.
  • J
    James GravesAug 26, 2025
    How do I resolve an Interlock Open error on my Aerco Benchmark 2000?
    • J
      Julie HickmanAug 27, 2025
      An Interlock Open error on your Aerco Boiler can be resolved by: checking for a jumper properly installed across the interlock terminals in the I/O box. If there are two external wires on these terminals check any Energy Management system to see if they have the units disabled (a jumper may be temporarily installed to see if the interlock circuit is functioning). Also, check that proving switch for any device hooked to the interlock circuit is closing and that the device is operational.
  • J
    Jared HillAug 25, 2025
    What causes a High Water Temperature error in my Aerco Benchmark 2000?
    • H
      hsuttonAug 25, 2025
      A High Water Temperature error in your Aerco Boiler can be caused by the same issues that trigger a High Water Temperature Switch Open error or a Temp HI Limit setting that is too low. Check the Temp HI Limit setting.

Summary

User Manual Installation, Operation and Maintenance

Chapter 1: Safety Precautions

1.1 Warnings & Cautions

General safety warnings and cautions applicable to installation and operation.

Chapter 2: Installation

2.8 Gas Supply Piping

Covers the installation and specifications for the gas supply piping.

Chapter 3: Operation

3.10 Start Sequence

Describes the step-by-step process for starting the boiler.

Chapter 4: Initial Start-Up

4.3 Natural Gas Combustion Calibration

Provides instructions for calibrating natural gas combustion for optimal performance.

Chapter 5: Mode of Operation

Chapter 6: Safety Device Testing

6.2 Low Gas Pressure Test

Procedure to test the low gas pressure safety fault detection.

6.3 High Gas Pressure Test

Procedure to test the high gas pressure safety fault detection.

6.4 Low Water Level Fault Test

Procedure to test the low water level safety fault detection.

6.5 Water Temperature Fault Test

Procedure to test the high water temperature safety fault detection.

Chapter 7: Maintenance

Chapter 8: Troubleshooting Guide

Table 8-1: Boiler Troubleshooting

A table listing fault indications, probable causes, and corrective actions.

Chapter 9: Boiler Sequencing Technology

Appendix D: Recommended Periodic Testing

Appendix H: Wiring Diagrams

Aerco Benchmark 2000 Specifications

General IconGeneral
BrandAerco
ModelBenchmark 2000
CategoryBoiler
LanguageEnglish