What should I do if my Aerco Boiler displays a Stepper Motor Failure?
- SSeth StevensSep 4, 2025
If your Aerco Boiler displays a Stepper Motor Failure, consider the following: * Air/Fuel Valve out of calibration: Refer to GF-112 (C-More O & M) and perform the Stepper Feedback Calibration procedure in Section 6, section 6.2.1. * Air/Fuel Valve unplugged: Check that the Air/Fuel Valve is connected to the Control Box. * Loose wiring connection to the stepper motor: Inspect for loose connections between the Air/Fuel Valve motor and the wiring harness. * Defective Air/Fuel Valve stepper motor: Replace stepper motor. * Defective Power Supply Board or fuse: Check DS1 & DS2 LEDs on Power Supply Board. If they are not steady ON, replace Power Supply Board. * Defective IGST Board: Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF every second. If not, replace IGST Board.