AES 7707 RF Subscriber 24
Part No. 40-7707 Rev. 3a 10/23/2017
Table 3. Limitations in Programming Features and Options
Topic
Feature or Option
Permitted
in UL
864/ULC
S559
Possible
Settings
Setting(s)
Permitted in UL
864/ULC S559
Comment
24 V DC Regulated Power
Supply
Y
24 VDC only
Y
FACP AUX Power
24 V DC Regulated
output.
Rechargeable
backup battery in
FACP.
12 V DC Regulated Power
Supply
N
N/A
N/A
12 V DC Regulated
Power Supply not
allowed.
AC Fail/DC Fail Report
Delay
Y
060, or R
(060 minutes,
or random
time between
060 min.)
0-60 (minutes)
R (random time
from 060
minutes)
System
Locally Announce AC
Fault/DC Fault
Y
Y or N
Y
Suppress AC Fault/DC
Fault
N
Y or N
N
Suppress Charger Fault
N
Y or N
N
Suppress Battery Fault
N
Y or N
N
Suppress Ground Fault
Reporting
N
Y or N
N
Inet Check-In
Y
1 minute to
24 hours
6 hours
maximum
Important! UL and NFPA standards do not allow remote programming of an installed Model 7707 subscriber
unless an authorized person is present at the unit to enable temporary remote programming capability. Note: When
any zone is configured as Fire, remote programming can be performed only up to 10 minutes after the subscriber is
reset or powered up.