AES 7707 RF Subscriber 41
Part No. 40-7707 Rev. 3a 10/23/2017
Available settings:
─ Random Delay ─ A random time ranging from 0‒60 minutes after 100 minutes of primary (16.5 V
AC) power loss. Enter R into the box to select this option.
─ Fixed delay ─ A specific time ranging from 1‒60 minutes after 100 minutes of primary (16.5 V
AC) power loss.
─ No Delay ─ Immediate transmission after 100 minutes of primary (16.5 V AC) power loss.
Locally Announce AC Fault
Important! UL-864 compliant fire alarm installations require that Locally Announce AC Fault be set to
Yes. See the Programming Options (UL Notice to Users) on page 23 for software settings permitted for the
following parameter.
Set Locally Announce AC Fault to Yes/No by clicking the Locally Announce AC Fault switch.
Suppress AC Fault Reporting
Important! UL-864 compliant fire alarm installations require that Suppress AC Fault Reporting be set to
No. See the Programming Options (UL Notice to Users) on page 23 for software settings permitted for the
following parameter.
Set AC Fault Reporting to Yes/No by clicking the AC Fault Reporting switch.
Suppress Battery Fault Reporting
Important! UL-864 compliant fire alarm installations require that Suppress Battery Fault Reporting be
set to No. See the Programming Options (UL Notice to Users) which starts on page 23 for software settings
permitted for the following parameter.
Suppress Charger Fault Report
Important! UL-864 compliant fire alarm installations require that Suppress Charger Fault Reporting
be set to No. See the Programming Options (UL Notice to Users) which starts on page 23 for software
settings permitted for the following parameter.
Set Suppress Charger Fault Report to Yes/No by clicking the Suppress Charger Fault Report
switch.
Power From: 24 V DC and Battery
Refer to the diagram shown in the Power Options section on page 10 for supply and connection
requirements.
Important! When using this selection, 24 V DC is the primary power source and the
battery is the secondary power source.