- In 0-10 V Fancoil units. Allows to control the minimum (1.5 V by default) and maximum (10 V by default) working
fan voltage of the controlled unit, in steps of 0.1 V. The minimum voltage corresponds with the desired lowest
speed for the unit and the maximum voltage corresponds with the highest speed. The medium speed
corresponds with the mid point between both of them.
Radio channel. It activates/deactivates the wireless association module of the system.
Information (only available for Think thermostats). Displays information about:
- Zone: Firmware, zone, association, actuator o communications status.
- System: Firmware, configuration and information about the controllers.
- Devices: Displays what elements are connected to the system.
- Webserver: Firmware, IP address, gateway, MAC and PIN.
Reset system (only available for master thermostat Blueface). Resets the system and returns to factory settings. To
reconfigure the thermostats, please check Initial setup
).
BACnet (only in installations with AZX6BACNET). This parameter displays the Device ID, the uplink port, the IP address,
the subnet mask and the Gateway IP and allows you to modify them. Press on the value you want to change, modify
it and then press to confirm. The values by default are:
- Device ID: 1000
- Port: 47808
- IP Address: DHCP
Protection mode (only available in Blueface thermostats and if the system detects an H2 error in the indoor unit). This
allows you to disable the delay in the closing of the motorized elements.
ZONE PARAMETERS
Associated outputs. It displays and allows you to select the control outputs associated with the thermostat.
Thermostat settings. Use this parameter to define the thermostat as Master or Zone.
*Note: It cannot be configured as Master if there is already another Master thermostat.
Use mode. The thermostats can be set in Basic or Advanced mode. They are set in advanced mode by default. These
are the parameters you can control in basic mode:
- On/Off.
- Set-point temperature.
- Operating mode (only if this is the master thermostat)
- Fan Speed
If you need to reset the thermostat to advanced mode, access the advanced configuration menu and then activate the
advanced use mode.
Control stages (only available in installations with AZCE6OUTPUT8 modules). This parameter is used to configure both
cooling and heating stages in a single zone or in all the zones. These are the features to be configured:
- Air: It activates the heating/cooling air in the zone.
- Radiant (only for heating stages): It activates the radiant heating in the zone.
- Combined (only for heating stages): It activates both air and radiant heating in the zone selected and allows the
user to select the desired heating stage that in the zone: Air, radiant or combined (see section Zone Configuration
menu - Blueface Thermostat, Heating stages). The zone will start using the heating air stage. Once the room
temperature reaches the differential preestablished (see parameter Hysteresis Conf.), the zone will activate the
radiant stage.
- Off: It deactivates the cooling/heating stage in the zone.

Table of Contents

Other manuals for Airzone FLEXA 3.0 IBPRO6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Airzone FLEXA 3.0 IBPRO6 and is the answer not in the manual?

Airzone FLEXA 3.0 IBPRO6 Specifications

General IconGeneral
BrandAirzone
ModelFLEXA 3.0 IBPRO6
CategoryThermostat
LanguageEnglish

Related product manuals