Error 16: Measurement error on the consumption meter
This issue do not allow the device to properly measure the power consumption of the air conditioning unit. To solve this issue:
1. Check that the amperometric clamp is properly connected to the air conditioning power supply cable.
Error 17: Communication error between Lutron Integration Gateway – Systems
The system loses communication with the Airzone Lutron Interface. Check that the gateway is properly connected to the
automation bus of the Main Board.
Error C-02: Main Control Board – Production Control Board communication error
This incident blocks the control of the zone. To solve this incident check:
1. Status of the control module of the radiant elements: Correctly powered.
2. Status of the Main Control Board: Expansion bus LEDs are operating properly.
3. Connection: Check the polarity of the connectors of the CCP and the Main Control Board of the system.