59
Error 16: Measurement error on the consumption meter
This issue do not allow the device to properly measure the power consumption of the air conditioning unit. To solve this issue:
1. Check that the amperometric clamp is properly connected to the air conditioning power supply cable.
Error 17: Communication error between Lutron Integration Gateway Systems
The system loses communication with the Airzone Lutron Interface. Check that the gateway is properly connected to the
automation bus of the Main Board.
Error C-02: Main Control Board Production Control Board communication error
This incident blocks the control of the zone. To solve this incident check:
1. Status of the control module of the radiant elements: Correctly powered.
2. Status of the Main Control Board: Expansion bus LEDs are operating properly.
3. Connection: Check the polarity of the connectors of the CCP and the Main Control Board of the system.