92 Rockwell Automation Publication 1756-UM022D-EN-P - May 2017
Chapter 5 Add, Configure, Monitor, and Replace CIP Safety I/O Devices
Scenario 1 - Replacement Device Is Out-of-box and Safety Signature Exists
1. Remove the old I/O device and install the new device.
2. Right-click the replacement safety I/O device and choose Properties.
3. Click to the right of the safety network number to open the Safety
Network Number dialog box.
4. Click Set.
5. Verify that the Network Status (NS) status indicator is alternating red/
green on the correct device before clicking Yes on the confirmation
dialog box to set the SNN and accept the replacement device.
6. Follow your company-prescribed procedures to functionally test the
replaced I/O device and system and to authorize the system for use.