Rockwell Automation Publication 1756-UM022D-EN-P - May 2017 93
Add, Configure, Monitor, and Replace CIP Safety I/O Devices Chapter 5
Scenario 2 - Replacement Device SNN Is Different from Original and Safety Signature Exists
1. Remove the old I/O device and install the new device.
2. Right-click your safety I/O device and choose Properties.
3. Click the Safety tab.
4. Click Reset Ownership.
5. Click OK.
6. Right-click the device and choose Properties.
7. Click to the right of the safety network number to open the Safety
Network Number dialog box.