Rockwell Automation Publication 6000-UM002E-EN-P - April 2018 23
Drive System Layout Chapter 2
Figure 14 - Isolation Transformer Primary and Secondary Winding Orientation
The secondary windings are brought out to corresponding vertical isolated stand-
offs on the body of the transformer (orientated U, V, and W from left to right as 
viewed from the front).
The U/W/V phase interconnections to the isolation transformer secondary 
windings are all on the front of the isolation transformer. The power cable 
connections to the power modules are made at the factory. Therefore, the field 
power cable connections need to be made at the isolation transformer secondary 
winding termination points, because the isolation transformer cabinet and power 
module cabinet are shipped separately (see publication 6000-IN006
).
Isolation Transformer Temperature Monitor
A discrete transformer temperature monitor is mounted on the LV door in the 
isolation transformer cabinet. There are two types of transformer temperature 
monitors, and the type used depends on the drive rating. Three temperature 
sensors are embedded in the isolation transformer. The monitor can be set to 
indicate an alarm condition or a trip condition, dependent on the temperature 
detected.
PRIMARY WINDING INPUT
SECONDARY WINDING OUTPUT
A (L1) B (L2) C (L3)
U
V
W
SECONDARY WINDING OUTPUT
U
V
W