126 Rockwell Automation Publication 6000-UM002E-EN-P - April 2018
Chapter 5 Preventative Maintenance and Component Replacement
Inspect the bus bars and cable connections. Check for any signs of overheating /
discoloration and tighten the bus connections to the required torque
specifications. Clean all cables and bus bars that exhibit dust build-up. Check for
corrosion, excessive temperature, or contamination.
Inspect Power Module Input and Output Power Connections
Verify that all Power Module input line cables and output bus connections are
properly torqued. Verify the output cables, VSB Cables and star connection
cables are properly torqued. Apply torque sealer if required. Check for corrosion,
excessive temperature, or contamination.
General
Review Firmware and Hardware
Verify the firmware version on the HMI. Contact Rockwell Automation to
determine whether there are any enhancements or changes made to the Drive
Hardware and Control that would be valuable to the application.
Verify that the HMI is operational. Check the status indicators on the Control
Unit in the LV Control cabinet register as normal.
Remove any dirt or foreign material. Wipe components with an anti-static cloth,
where applicable.
Inspect/Review Spare Parts
Inspect and review the spare parts shipped with the drive (see the packing list if
applicable). Check for signs of damage, dirt, or foreign material.
ATTENTION: Ensure there is no power to the drive and wear an anti-static
wristband.
ATTENTION: Some circuit boards can be destroyed by static charges. Use of
damaged circuit boards may also damage related components. Use a grounding
wrist strap when handling sensitive circuit boards.
ATTENTION: Due to the characteristics of DC capacitors, rejuvenation is
necessary on power module DC capacitors if the power module has not been
energized in the last one year. Therefore the spare power modules need to be
energized annually.

Table of Contents

Other manuals for Allen-Bradley PowerFlex 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 6000 and is the answer not in the manual?

Allen-Bradley PowerFlex 6000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 6000
CategoryDC Drives
LanguageEnglish

Related product manuals