22 Rockwell Automation Publication 6000-UM002E-EN-P - April 2018
Chapter 2 Drive System Layout
Figure 13 - Isolation Transformer Cabinet, Type C (Junction cabinet applied for cable connection)
Isolation Transformer
The primary winding of the isolation transformer is rated for the voltage of the 
distribution system. It is connected to the distribution system by the incoming 
line power cables. The secondary windings of the isolation transformer are 
connected to the inputs of the power modules. The secondary low voltage 
winding is to feed the low voltage power modules.
There are between 9 and 27 three-phase secondary side windings, dependent on 
the motor voltage requirements from 2.3 kV to 11 kV. The phase relationship 
between the secondary windings are optimized to provide the highest reduction 
of line side harmonics.
The isolation transformer’s three-phase primary coils are oriented A, B, and C 
from left to right, as viewed from the front. The secondary windings are also 
divided into three principal sections from top to bottom. The upper third are to 
feed the power modules in the U output phase. The middle third are to feed the 
power modules in the V output phase. The bottom third are to feed the power 
modules in the W output phase (Figure 14
).
L3 L1
WV U
L2
Junction 
cabinet
Incoming line 
power cable 
connections
Outgoing motor 
power cable 
connections
Isolation 
Transformer
Front View Side View