Page 111
Metal SP1X
Metal SP16X
Mechanical
Dimensions Cabinet: ( mm )
505 (H) x 407 (W) x 150
(D)
Includes window outer
door
1200 (H) x 625 (W) x 240
(D)
Includes window outer
door
Material
1.2mm Mild Steel
1.2mm Mild Steel
Environmental
Temperature:
Humidity:
IP rating
-5ºC to + 40ºC
25% to 95% non condensing
IP30
Mains Input
Input Voltage:
Protection (Quick Acting Fuse):
5 AMP Supply
18 AMP Supply
Minimum Cable Requirements:
195 - 264VAC
2Amp 3AG Slow Blow
N/A
Not less than 0.75mm²
195 - 264VAC
N/A
5A 3AG Slow Blow
Not less than 0.75mm²
Power Supply
Operating Voltage Range:
Power Supply Ripple Voltage:
Power Supply Output Current:
Imax A
Imax B
Protection
20 - 28.2VDC
<250mV
5.6Amps
3Amps
5.5Amps
Current Limiting
20 - 28.2VDC
<250mV
18Amps
Current Limiting
Batteries / Battery Charger
Charger O/P Voltage
(Temp compensated):
Approved LPCB Battery:
Battery Type:
Max Battery Capacity:
Max Charger Current Limited:
Battery Supply Current Limited:
Battery Low:
Battery Discharged Cut-off Voltage:
Max Battery Resistance
26.6-28.2VDC
(27.3VDC nom @ 20°C)
2x12V Sealed Lead Acid
18AH
1.25A
3A and 2A PTC
<23VDC
<21VDC
0.75
26.6-28.2VDC
(27.3VDC nom @ 20°C)
2x12V Sealed Lead Acid
40AH
2A
3A and 2A PTC
<23VDC
<21VDC
0.43
Panel
Quiescent Current ( QI ) 1 Loop
220mA
Max Number of Zone LEDs:
64
128 +
Loop
Maximum number of Loops:
Maximum Number of Devices:
Loop Current
Cabling Requirements:
Fault supervision:
4
126 / loop
500mA / loop
2 core 1.5 -2.5mm² Max
length 1km
O/C, S/C , over current
16
126 / loop
500mA / loop
2 core 1.5 -2.5mm² Max
length 1km
O/C, S/C , over current
Outputs
Supervised Alarm (Current Limited)
Alarm / Fault Relay Contacts
Auxiliary VDC Protected
Cabling Requirements:
24VDC @ 1A Max O/C, S/C, 10K EOL
24VDC @ 1A
24VDC @ 2A
2 core 1 -2.5mm2 Max length 1km
Inputs
Supervised
Cabling Requirements:
O/C, S/C, 10K EOL
2 core 1 -2.5mm2 Max length 1km
Communications
Add-on Module Internal to FACP
External to FACP
RS485
RS485