8.9 Programming
Press To display the Level III Programming Menu.
ON SITE PROGRAMMING MENU
0: CONV ZONE 1 :DEVICE 2:INPUT 3: OUTPUT
4: PANEL BASED MCP 5:SUB ADDRESS
6:ZONE PROGRAMMING
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 65: Programming Menu
8.9.1 Conv (Conventional) Zone
Press CONV ZONE:
Key in the zone number and enter or change the description (DESC) by pressing
buttons to move the flashing underline or curser. The numeric buttons multiple times to access
characters while at the same time using
EDIT Zx DESC AND TYPE STRINGS
DESC < ZONE >
TYPE<
ALPHA KEYS ARE ACTIVE
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 66: Zone Description & Type Programming
Press to move to the TYPE field or edit the information.
Press to move between fields use the reciprocal button
By going through all the fields a second screen can also be accessed to show the Output options.
Press to step through these fields.
EDIT ZX BRIGADE OPTIONS AND CONFIG
ALRM: Y/N BELL: Y/N AUX: Y/N SPRK: Y/N
AIF: Y/N
ALARM LED: Y/N CONFIG: LATCHING
Use < or > to change setting
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 67: Brigade Options
The buttons are used to set the Y/N field, which is the selected Zone that will
activate the Brigade Options ALRM, BELL etc and Config.