8.5 TESTS
Press to access the TESTS menu. Note this is an Access Level 3 function only.
TESTING MENU
0: WALK TEST 1:LOOP TEST
2: DEVICE LED TEST
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 58: The Testing Menu
Press to initiate a WALK TEST:
WALK TEST MENU
0: NEW ZONE WALK TEST
1: NEW ZONE SILENCE WALK TEST
2: VIEW ZONE WALK TEST
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 59: The Testing Menu
When in walk test the indicator is on.
Press LOOP TEST requires the operator to select a LOOP for DIAGNOSTIC TESTING
Entering the LOOP number and pressing will initiate the DIAGNOSTIC TEST.
Note: The LED’s on the Brigade Board will indicate which leg is being tested.
The tests displayed are;
TESTING SIDE A IDENTIFING DEVICES on SIDE A, and
TESTING SIDE B IDENTIFING DEVICES on SIDE B.
Once the testing is completed the final screen will display the number of devices found and tested on
the LOOP and a Reset is requested to return the system to normal.
Note: If the data is not entered within 2 minutes the screen will time out and return to the
DEFAULT SCREEN.
Note: A Loop Test needs to be conducted after a short / open circuit has occurred, corrected and
cleared to return the panel to its default Normal status otherwise the panel will display a loop fault.
Press to initiate a DEVICE LED TEST:
This allows the user to turn on a device LED. Cancel out of the Device LED test screen will
automatically turn off the device LED. If the device LED test screen is left on after 30 minutes the LED
will turn off and the panel return to the Normal screen.