EasyManua.ls Logo

Ampac FireFinder PLUS - Way Relay Board; Internal Relay Board

Ampac FireFinder PLUS
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 64
12.9 8 Way Relay Board
The Relay Board (BRD25EWRB) provides 8 programmable relays with 30VDC 1 Amp voltage free
change over contacts for control or monitoring purposes and comes fitted for internal or external FACP
use.
The functionality and programming of the relays is similar to the relays on the main board of the FACP.
By default the relays default to Common Alarm functionality.
All terminal points are protected.
The board switches the relays as determined by the panel. The relays can be controlled by:
Zones Alarm
Group Alarm
Device Alarm
Internal Output
Panel Output
Loop Output
Panel Input
Loop Input
Reset relay is activated for 3 seconds when reset depressed
12.9.1 Internal Relay Board
Fit EOL Termination
Link 1 if Last Module
on Comms Bus
Address SW
(See Note)
Not used optional 27VDC
RS485 Control / 27VDC
Comms In
CN2
CN1
CN3
CN4
ON
+
-
TB8
TB7
TB6TB5
TB4
TB3
TB2
TB1
SW1
O/P 8
N/C
COMN/0
O/P 7
N/C
COMN/0
O/P 6
N/C
COMN/0
O/P 5
N/C
COMN/0
O/P 4
N/C
COMN/0
O/P 3
N/C
COMN/0
O/P 2
N/C
COMN/0
O/P 1
N/C
COMN/0
1 2 3 4
ON
TB8
TB7
TB6TB5
TB4
TB3
TB2
TB1
O/P 8
N/C
COMN/0
O/P 7
N/C
COMN/0
O/P 6
N/C
COMN/0
O/P 5
N/C
COMN/0
O/P 4
N/C
COMN/0
O/P 3
N/C
COMN/0
O/P 2
N/C
COMN/0
O/P 1
N/C
COM
N/0
N/0 = Normally Open
COM = Common
N/C = Normally Closed
RS485 Control / 27VDC
Comms Out
Figure 90: Internal 8 Way Relay Board Front View showing connectors and Address Switch
Relay Connections
Terminal/s
Function
TB1 to 8
N/O = Normally Open,
C = Common
N/C = Normally Closed
Relay 1 to 8
Note: See Section 17 for Addressing Details (SW1)

Table of Contents

Other manuals for Ampac FireFinder PLUS

Related product manuals