AUX air conditioner service manual
37
indoor fan stops immediately.
Overheated protection
a)When heating function runsif TETE9 and last for 10secondsthe outdoor fan stopsif TETE10
and last for 10seconds, then stop the compressorWhen TE< TE11 and after the 3 minutes protection
delay, the compressor resumes normal working.
b.This temperature protection is valid only when the TE temperature sensor runs normally.
The auxiliary electric heating function
The electric heating function may not start unless the heating mode runs normally e.g. the
compressor starts, the outdoor fan runs, the four-way valve is electrified, the indoor fan is on as well
as the availability of the below conditions:
a)TE < TE12
b)TA < TA3
c)TS – TA 3℃;
d)The compressor runs continuously in heating mode for 4min
The auxiliary electric heating may withdraw working if meet one of the below conditions:
a)TA > TA3
b)TS – TA < 2℃;
c)TE > TE11
If one of the compressor, four-way valve and indoor fan doesn’t work or there is error feedback
from the indoor fan, the auxiliary electric heating withdraw from work;
If the sensor of TE is damaged and the turn-off without non-electricity occurred in the ongoing
auxiliary electric heating process, the indoor fan turns in the low speed wind operation for 40 seconds
and stops
Intelligent defrosting function
Under the operation of the intelligent defrosting mode, t he air-conditioner starts the defrosting
process if satisfying the requirement of one of the below five conditions (the sub-conditions included
shall all be satisfied). During the defrosting process, the sleeping light is twinkling:
a) The outdoor fan starts the overloading protection and the outdoor fan stops;
b) Restart the outdoor fan after stop and the continuous running time over than 10 minutes;
c)The accumulated operation time of the compressor 45min
d)The continuous operation time of the compressor20min
e)TE TE12
a) After the 5 minutes operation of the heating mode or 5 minutes later after the defrosting process,
starts the capture motion for the max. difference value between TE and TA, when the difference
between TE and TA being reduced up than X min and the time lasts3min
b)The continuous operation time of the compressor5min
c)The accumulated operation time of the compressor45min
d)TE TE12
NoteWhen the wind speed correction available, if the wind speed of the indoor fan drops by one gear,