AUX air conditioner service manual
When TE is in rise status, if Te<30,the indoor fan turns off;30TE38,the indoor fan runs
at low fan speed;Te38, the indoor fan runs at setting wind speed;
When Te in fall status, if TE>34,the indoor fan runs at the setting fan speed;28℃<TE34,the
indoor fan runs at the low fan speed;TE28℃,the indoor fan turns off.
Picture 1
Anti-cold wind function when compressor stops
When TE is in the fall status, if TE>30,the indoor fan runs at low fan speed;TE30≤℃,indoor
fan turns off;
When TE is in the rise status, if TE35, the indoor fan runs at low fan speed; TE35<, indoor
fan turns off;
Picture 2
Residual-heat removing function after air-conditioner stops
When TE35℃,the indoor fan runs at the low fan speed, if35,the indoor fan turns off, and
air-conditioner stops for starting the process of residual heat removal and last for 10seconds, within
the 10second of process of residual heat removal, if TE< 35, the indoor fan turns off at once.