AUX air conditioner service manual
226
The “running” light and “swing” light are twinkling and last for 0.5/0.5 second, the other indication
lights are invariable, and the system turns off.
4. ASF-H24B4/B, ASF-H41A5/B faults display and protection display:
Fault of the Indoor temperature sensor
System turns off; the panel displays “E1”
The fault of the outdoor tube temperature sensor on the indoor panel
System doesn’t turn off; the panel displays“E2”.
Fault of the interior tube temperature sensor
System doesn’t turn off, the panel display “E3”runs under the mode without interior temperature
sensorWhen under the heating mode, there is no overheating protection, anti-cooling wind protection
and residual heat removal function, the indoor fan starts running at the setting fan speed 30 seconds
later after the compressors starting, and stops after 30 seconds running at the ultra low fan speed
without compressor; When under the refrigeration mode, there is no anti-freezing protection.
Communication fault
The system turns off or can’t start, the panel displays “E4”which may be displayed under either on or
off status.
The protection of outdoor reverse phase and failure of phase:
System stops, and the panel displays “E6”
Heating and defrosting
The “defrosting” indication light on the panel is twinkling, (0.5/0.5) the other are invariable.
When the indoor tube temperature available, the indoor refrigeration anti-freezing protection
The “running” light and “cooling” light on the panel are twinkling (0.5/0.5), the other are invariable.
When the indoor tube temperature available, the indoor heating overheating protection
The “running” light and “heating” light on the panel are twinkling (0.5/0.5), the other are invariable.
When the indoor tube temperature available, the indoor heating long time anti-cooling wind
protection
The “running” light on the panel is twinkling (0.5/0.5), the other are invariable.
5ASW-(H)18A4/III fault display and protection display
Damage to the outdoor coil pipe
The timing light on the panel twinkles one time/second.
The damage to the indoor temperature sensor
The timing light on the panel twinkles one time/8 seconds.
The damage to the indoor coil pipe sensor
The timing light on the panel twinkles two times/8 seconds.
Heating and defrosting
The sleeping light twinkles (0.5/0.5 second
Refrigerating anti-freezing protection
The operation light and the timing light of the panel twinkle (0.5/0.5 second
6Heating anti-overheating protection
The “running” light and “sleeping” light are twinkling0.5/0.5second
Heating long time anti-cooling wind protection
The “running” light is twinkling0.5/0.5second
6FS(Y)DS(Y) ZVYCSY model air-conditioner faults display and protection display