AUX air conditioner service manual
45
speed can be adjusted through the button of “wind speed selection” in the selection of the four wind
speeds type, such as strong wind, high wind, low wind and mute wind. The four-way valve always is
closed under this mode. The other action is as following:
When TA - TS1℃,after the compressor meet the 3 minutes delay protection, the compressor and
the outdoor fan start running;
When TA = TSmaintain the previous status;
When TA - TS-1℃,after the compressor meet the 3 minutes protection condition, the compressor
and the outdoor fan turn off;
The setting wind speed can be adjusted by the remote control during the ongoing cooling process,
and the interior fan still retains working;
When the status of TE 0 last for 10 seconds and the compressor keeps working for above than 5
minutes, turn off the compressor and outdoor fan, the indoor fan keep working according to the setting
wind speed; Quit from such protection if TE 7;
This mode includes the functions of timing, sleeping, auto-restart (optional), negative ion (optional),
I feeloptional;
When the cooling ongoingthe button of the “Swing” can control the swing and stop of the
horizontal air-blade;
Automatic wind-speed control
TA - TS3℃,wind-speed works at high wind;
TS +1TATS +3℃,wind-speed works at middle wind;
TATS1℃,wind-speed works at low wind;
Without 3 minutes delay when the wind speed turns into the high wind from the low wind, otherwise
with 3 minutes delay;
Being initially electrified, the compressor doesn’t have the 3 minutes delay protection, the outdoor
fan starts after 2 seconds of the compressor’s start; When TSTA set by the remote control, the
compressor turns off immediately with no need of 3 minutes delay protection;
When TE 64 and after last for 10seconds, the compressor and the outdoor fan turn off; If meet
the 3 minutes delay condition and TE 62, the compressor can start normally. When the
air-conditioner is under overheating protection, if the wind speed setting is by hand, the indoor fan
unit will run at the setting wind speed; if the wind speed setting is automatic, the indoor fan unit runs
at the low fan speed.
Dehumidification mode
The four-way valve always turns off when the dehumidification mode is ongoing. The control range
of the temperature is: 16 - 32.