6-29
Chapter 6. LIST OF DISPLAYS AND SETTING DATA
User Function bank
Bank selection:
Display Item Contents
Initial
value
User
level
Notes
User Function 1 Each setting is set on the upper
display.
The following shows the setting
exceptions:
----
: Not registered.
P-
_
: Proportional band of
currently used PID group
I
-
-
: Integral time of currently
used PID group
d-
-
: Derivative time of currently
used PID group
rE-
-
: Manual reset of currently
used PID group
OL-
-
: Output low limit of
currently used PID
OH-
-
: Output high limit of
currently used PID group
P-
-
C
: Proportional band for cool
side of currently used PID
group
I
-
-
C
: Integration time for cool
side of currently used PID
group
d-
-
C
: Derivative time for cool side
of currently used PID group
OL.
-
C
:
Output low limit for cool side
of currently used PID group
OH.
-
C
: Output high limit for cool
side of currently used PID
group
----
1
It is possible to register only
the settings, which can be
displayed.
(Example: Manual reset
of the PID constant can
be registered when the I
(Integral time) is set at “0”.)
The registered setting is
added to the end of the
display order of the basic
display.
User Function 2 ----
1
User Function 3 ----
1
User Function 4 ----
1
User Function 5 ----
1
User Function 6 ----
1
User Function 7 ----
1
User Function 8 ----
1

Table of Contents