13-1
Chapter 13. SPECIFICATIONS
Specifications
PV input
Thermocouple: K,J,E,T,R,S,B,N (JIS C1602-1995)
PL II (Engelhard Industries Data (ITS90))
WRe5-26 (ASTM E988-96(Reapproved 2002))
Ni-NiMo (ASTM E1751-00)
PR40-20 (Johnson Matthey Data)
DIN U,DIN L (DIN 43710-1985)
Gold iron chromel (Hayashidenko Data)
Resistance temperature detector (RTD):
Pt100 (JIS C1604-1997)
JPt100 (JIS C1604-1989)
DC voltage:
0 to 10 mV, -10 to +10 mV, 0 to 100 mV,
0 to 1 V, 1 to 5 V, 0 to 5 V, 0 to 10 V
DC current: 0 to 20 mA, 4 to 20 mA
Selection of input type: A desired type can be selected (full-multi range).
Sampling cycle time: 100 ms
Indication accuracy: ±0.1 %FS±1 digit, ±0.2 %FS±1digit in the negative area of the thermocouple
(Specified by the input conversion at an ambient temperature of 23±2 °C)
However, the following ranges have different values:
Sensor type B (range 17):
±4 %FS at 260 °C or less, ±0.4 %FS at 260 to 800 °C, ±0.2 %FS at 800 to
1800 °C
The low limit for indication is 20 °C. However, if ROM version 1 of the
instrument information bank (
I
d02
) is prior to 2.04, the low limit for
indication is -180 °C.
Sensor type R (range 15), sensor type S (range 16):
±0.2 %FS at 100 °C or less, ±0.15 %FS at 100 to 1600 °C
Sensor type PR40-20 (range 23):
±2.5 %FS at 0 to 300 °C, ±1.5 %FS at 300 to 800 °C, ±0.5 %FS at 800 to
1900 °C
Sensor type golden iron chromel (range 26): ±1.5 K
Sensor type Pt, JPt (RTD) (range 55 to 62): ±0.15 %FS
Sensor type 0 to 10 mV (DC voltage) (range 81): ±0.15 %FS
Note: For the indication accuracy of the unit in combination with zener barriers,
see chapter 4
Cold junction
compensation
accuracy:
±0.5 °C (at an ambient temperature of 23±2 °C)
±1.0 °C (at an ambient temperature of 15 to 35 °C)
±1.5 °C (at an ambient temperature of 0 to 15 °C or 35 to 50 °C)
Cold junction
compensation method:
Compensation inside or outside (only at 0 °C) the measuring instrument
can be selected.
PV bias: -1999 to +9999 or -199.9 to +999.9
Thermocouple (T/C) input
Input bias current: +0.2 μA (flows from terminal A.)
Burnout indication:
Upscale + AL01
Diameter of the applicable
thermocouple or
compensating wire:
0.3 to 0.65 mm
Allowablr input voltage: -0.5 to +12 V