11-1
Chapter 11. CALIBRATION
CAUTION
Do not change the mode to the calibration mode while the control object is being operated.
When this unit is put in the calibration mode, the control output and event output enter the
fixed status and they do not function. Always start the calibration by considering this point
carefully.
Handling Precautions
It may be required to disconnect and reconnect the wiring for calibration.
At this time, strictly observe the warnings and cautions about wiring stated in
Chapter 4, WIRING.
This chapter describes how to calibrate this unit.
To calibrate this unit, the SLP-C35 Smart Loader Package is required.
Starting the calibration
Start up the SLP-C35 Smart Loader Package. On the menu screen, select
[Calibration (J)] from the [Menu (M)] pull-down menu. The [Calibrate]
confirmation screen will appear.
On this screen, select [OK]. The Calibration screen will appear and this unit enters
the calibration mode.
When this unit is in the calibration mode, “
tESt
” will appear on the lower display.
However, note that another message appears when inspecting the LED.
Handling Precautions
Azbil Corporation shall not be held responsible for any defects arising
from improper calibration made by the customer.
To return the unit to the calibration status of the default settings before
shipment during calibration, follow the steps below. From the pull-down
menu, select [Command] [Data retrieval]. The data, which has been
calibrated, is disposed of and the data is then returned to the default
settings before shipment. If this operation is performed accidentally
during calibration, all contents, which have been calibrated by the
customer, will be lost.
Exiting the calibration
To exit the calibration, perform either of the following operations:
(1) On the Calibration screen of the Smart Loader Package, select [Quit (Q)] from
the [File (F)] pull-down menu.
(2) Click [X] at the upper right corner of the Calibration screen to close the screen.
The screen will be returned to the menu screen and the unit also returns to the
normal mode.
Handling Precautions
If the loader cable is disconnected before starting the calibration exit
operation with the Smart Loader Package, this unit is continuously kept in
the calibration mode. At this condition, turn OFF the power, and turn it ON
again. The unit will return to the normal mode.