Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
SP setup in operation display mode
The set value for LSP in use of LSP1 to 8 can be set.
The LSP set value is different from the SP display value during SP ramp. However,
the set value is displayed while the key is being operated to change the setting.
Item (Bank) Display Contents Initial value User level
SP (Operation display) PV is
shown on
the upper
display.
SP low limit to SP high limit U 0 U Basic,
Standard,
High function
• When [bit 1: SP display] of [
C74
: PV/SP display setup] is set at "1" (display is
provided), the display and setting can be made.
• The SP cannot be set in the RSP mode.
LSP system group
The LSP system group can be selected.
Item (Bank) Display Contents Initial value User level
LSP system group
(Setup bank)
1 to 8 1 Basic,
Standard,
High function
SP ramp type
Either the standard ramp or multi-ramp can be selected.
Additionally, for details about step operation,
5 - 6 Step Operation (p.5-43).
Item (Bank) Display Contents Initial value User level
SP ramp type
(Setup bank)
1: Multi-ramp
2: Step operation The step operation is
stopped when the power is turned ON
again (READY).
3: Step operation The step operation is
recovered when the power is turned ON
again.
0 High function
• When this setting is set at “0”, the ramp-up and ramp-down use only one setting
group (SP ramp-up and SP ramp-down of parameter bank) even though one LSP
group or multiple LSP groups are used.
• When this setting is set at “1”, the ramp setting (ramp 1 to 8 of SP bank) common
to the up/down to be set by LSP group is used.
RSP input range type
The RSP input signal type can be selected.
Item (Bank) Display Contents Initial value User level
RSP input range type
(Setup bank)
0: 4 to 20 mA
1: 0 to 20 mA
2: 0 to 5 V
3: 1 to 5 V
4: 0 to 10 V
0 Basic,
Standard,
High function
• When the model provides the RSP input, the display and setting can be
performed.