Introduction Azbil Corporation
1-10 MagneW FLEX+/PLUS+ Electromagnetic Flowmeter Detector
1.3.6: Approval of this device
Overview
If 1/2 NPT wiring connection is selected, this device functions as an FM/CSA, non-
incendive -approved model. In this case, the installation standards described in this
section must be followed.
Installation of this device
FM/CSA Nonincendive model
THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS
(A, B, C, D), CLASS II/III, DIVISION 2, GROUPS (F, G), OR NON-HAZARDOUS
LOCATIONS ONLY.
CAUTION
(1) Power supply and internal voltage of ordinary equipment to the earth shall not
exceed 250 V AC 50/60 Hz, 250 V DC in case on normal / formal conditions.
(2) Ambient temperature is from -25 to 60°C
(3) Process temperature is from -40 to 160°C (Remote model).
Process temperature is from -40 to 120°C (Integral model)