Azbil Corporation  Safety
MagneW FLEX+/PLUS+ Electromagnetic Flowmeter Detector  iii
 CAUTION
If the pipe is not lled, output errors will occur.
 CAUTION
Do not rotate the unit more than 180° (one half rotation). Any further rotation can 
disconnect wiring.
After removing the screws, do not pull on the terminal box. You can break the 
lead wire.
When you move the terminal box, make sure the O-ring remains in the groove to 
insure an air-tight seal when the unit is reassembled.
 CAUTION
Before installing the detector, make sure any foreign matter is ushed from 
the interior passage of the detector. Residual foreign matter could cause output 
uctuations.
Do not touch the electrodes or allow oil or fat to come into contact with them to 
avoid output uctuations.
Align the direction mark on the detector in the direction of the liquid ow. 
Misalignment can result in a negative output.
 CAUTION
The correct fastening torque must be used to prevent leakage. To avoid damage to 
the detector, do not exceed the listed fastening torque.
 CAUTION
Before installing the detector, make sure that the pipe is exactly straight and 
centered. Any irregularity could cause leakage or other hazards.
 CAUTION
Never attempt to force the detector between two anges if the space is too narrow. 
It can damage the detector.
 CAUTION
Make certain the bore diameters of the pipe and the detector are exactly the same 
and install the detector so that the gasket does not protrude into the internal bore 
of the pipe, as this could result in leakage or other hazards.