3-8 Basic Installation MN1919
3.2.6 Derating characteristic - 9A model
The following derating characteristics are for model FMH2A09TR-EN23.
0
1
2
3
4
5
6
7
8
9
30 35 40 45 50 55
Ambient temperature (°C)
Three-phase AC supply
Natural cooling
1m/s forced air
1.5m/s forced air
2.5m/s forced air
3.5m/s forced air
Notes:
Load power factor = 0.78.
Overload limit for model FMH2A09TR-EN23 is 18A.
Rated output currrent (A
rms
)
Ambient temperature (°C)
Single-phase AC supply
Rated output currrent (A
rms
)
0
1
2
3
4
5
6
7
8
9
30 35 40 45 50 55
Natural cooling
1m/s forced air
1.5m/s forced air
2.5m/s forced air
3.5m/s forced air
3.2.7 Overtemperature trips
The MicroFlex contains internal temperature sensors that will cause it to trip and disable if the
temperature exceeds 80°C on the 1A or 3A models, or 75°C on the 6A and 9A models. This
limit can be read using the TEMPERATURELIMITFATAL keyword - see the Mint help file for
details.

Table of Contents

Other manuals for Baldor MicroFlex

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Baldor MicroFlex and is the answer not in the manual?

Baldor MicroFlex Specifications

General IconGeneral
BrandBaldor
ModelMicroFlex
CategoryAmplifier
LanguageEnglish

Related product manuals