3.4.5 Recommended fuses and wire sizes
Table 3 describes the recommended fuses and suitable wires sizes to be used for power
connections.
Continuous AC Input Fuse Minimum
Catalog
Table 3 - Protection device and wire ratings
Note: All wire sizes are based on 75°C (167°F) copper wire. Higher temperature smaller
gauge wire may be used per National Electric Code (NEC) and local codes.
Recommended fuses are based on 25°C (77°F) ambient, maximum continuous
control output current and no harmonic current. Earth/ground wires must be the
same gauge, or larger, than the Line wires.
3.4.6 Drive overload protection
The MicroFlex will immediately trip and disable if there is an overload condition. The parameters for
managing drive overloads are configured automatically by the Commissioning Wizard (see section
6.2.3). If they need to be changed, use the Parameters tool in Mint WorkBench (see section 6.3.2).