1. Start Siemens SIMATIC Manager.
2. Select an existing project and open it.
3. Select the Station (PLC) from the Object Hierarchy list.
Figure 154. Object Hierarchy List
4. Double-click the Hardware icon in the Station level window to open the Hardware configuration window.
Figure 155. Double-click the Hardware Icon
5. Right-click on the PN-IO line in the CPU module of the Station window and select
Insert PROFINET IO System
.
6. In the Parameters tab of the Ethernet interface properties window type in the IP Address and Subnet Mask of the
PLC.
7. Select the Ethernet subnetwork from the box at the bottom of the Ethernet interface properties window. If no
suitable network is shown, click the New button to add one, then click OK.
Figure 156. Add New Network
8. Click iVu BCR in the Hardware catalog and drag and drop onto the PROFINET IO system connection.
Figure 157. Add iVu BCR to the PROFINET IO System Connection
The device is connected to the system.