Page #64 background imageLoading...
Page #64 background image
Operation
64
RCMS460-490_D00067_03_M_XXEN/12.2017
Overview of available functions
4. Response delay t(on)
Response delay starts when a new alarm has been triggered.
Setting range: 0…999 s.
Resolution of settings:
Setting range Resolution of setting
0…50 ms 5 ms
60…200 ms 10 ms
250…500 ms 50 ms
600 ms …2 s 100 ms
2.5…5 s 0.5 s
6…20 s 1 s
25…50 s 5 s
60…200 s 10 s
250…500 s 50 s
600…999 s 100 (99) s
Measuring function
(selectable)
RCMS…-D/-L
Channel
1…12
RCMS…-
D4/-L4,
Channel
1…8
RCMS…-
D4/-L4,
Channel
9…12
I/I
Δn
: 6 mA…20 A
(42…2000 Hz)
type A
</>/OFF </>/OFF ---
I: 100 mA…125 A
(42…2000 Hz)
--- --- </>/OFF
I/I
Δn
: 10 mA…10 A
(0…2000 Hz)
type B
</>/OFF </>/OFF ---
1/0 1/0/OFF 1/0/OFF ---