EasyManuals Logo

Bender RCMS460 User Manual

Bender RCMS460
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #82 background imageLoading...
Page #82 background image
Tests, service, troubleshooting
82
RCMS460-490_D00067_03_M_XXEN/12.2017
7.3 Troubleshooting
7.3.1 Display device error
An "error code" is displayed if a fault occurs. Please have this device informa-
tion to hand if you should need to contact us for assistance by telephone.
Display in the event of a fault
xx = Error code
Error
code
Description
1 Measurement technique: Fault parameter memory (EEPROM/
FLASH).
2 Measurement technique: Fault data memory (RAM).
4 Measurement technique: No boot loader available.
11 Measurement technique: Device not calibrated.
12 Measurement technique: Wrong measurement p.c.b., incor-
rect mounting.
13 Measurement technique: Hardware error after performing a
self test.
71 BMS interface: No master available resp. has not been que-
ried by a master for five minutes.
72 BMS interface: Fault RS-485 interface.
712 Measurement technique: Device error on all channels (12/12).
RCMS…-D RCMS…-L…
Device error: xx Er
xx (alternately displayed)