Operation
71
RCMS460-490_D00067_03_M_XXEN/12.2017
2. Overwrite
Yes If the memory (300 measuring values) for this measuring
channel is full, the oldest measured value is deleted to create
space for the new measured value entry.
No Data logger records 300 measured values then stops.
3. Delete
The recorded measured values of this measuring channel are deleted. To pre-
vent unwanted execution of this function, the entry must be confirmed once
more.
6.6.6.7 Settings menu 7: Language
Select the language for menu and alarm texts. Setting options depend on the
software version:
German, English, French D256 V2.3x
German, English, Swedish D339 V2.3x
German, English, Italian D403 V2.3x
Setting options depend on the software version:
6.6.6.8 Settings menu 8: Interface
Set the RCMS… own BMS bus address. The device with address 1 has the mas-
ter function on this bus. There must be one device with address 1 in each
RCMS system.
Setting range: Address 1…90
6.6.6.9 Settings menu 9: Alarm addresses
Setting of the bus addresses (1…150) externally connected to the BMS bus,
the alarm messages of which are to be displayed as standard messages on this
RCMS…-D. Set the addresses of devices whose messages are to be displayed
to "on".
Addresses set to "on" are monitored for presence on the BMS bus; if a device
cannot be found on the bus, a corresponding message will appear. The RCMS
address is automatically set to "on".