Page #86 background imageLoading...
Page #86 background image
Data
86
RCMS460-490_D00067_03_M_XXEN/12.2017
8.3 Technical data
Insulation coordination acc. to IEC 60664-1/IEC 60664-3 for the versions:
a)RCMS4x0-D1
Supply voltage U
S
.................................................................................DC 24…75 V/AC 24…60 V (AC/DC ±20 %)
Supply voltage frequency...........................................................................................................................DC, 50/60 Hz
Rated insulation voltage....................................................................................................................................... 100 V
Overvoltage category/pollution degree....................................................................................................................III/3
Rated impulse voltage......................................................................................................................................... 2.5 kV
Protective separation (reinforced insulation) between.................................. (A1, A2) - (k1, l…k12, R, T/R, T, A, B)
Voltage test acc. to IEC 61010-1 ......................................................................................................................1.344 kV
Rated insulation voltage....................................................................................................................................... 250 V
Overvoltage category/pollution degree....................................................................................................................III/3
Rated impulse voltage............................................................................................................................................. 4 kV
Basic insulation between:............................................................................... (A1, A2), (k1, l…k12, R, T/R, T, A, B) -
(C11, C12, C14), (C21, C22, C24), (11,14), (21,24), (31,34), (41,44), (51,54), (61,64), (71,74), (81,84),
(91,94),(101,104), (111,114), (121,124)
Basic insulation between: ............................................. (11, 14) - (21, 24) - (31, 34) - (41, 44) - (51, 54) - (61, 64)
Voltage test acc. to IEC 61010-1 ...................................................................................................................... 2.21 kV
Rated insulation voltage ....................................................................................................................................... 250 V
Overvoltage category/pollution degree....................................................................................................................III/3
Rated impulse voltage............................................................................................................................................. 6 kV
Protective separation (reinforced insulation) between.........................................(C11, C12, C14) - (C21, C22, C24) -
(11, 14, 21, 24, 31, 34) - (41, 44, 51, 54, 61, 64) - (71,74) - (81,84) - (91,94) - (101,104) - (111,114) - (121,124)
Voltage test acc. to IEC 61010-1 ...................................................................................................................... 3.536 kV