EasyManua.ls Logo

Bender RCMS460 - Technical Data

Bender RCMS460
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data
86
RCMS460-490_D00067_03_M_XXEN/12.2017
8.3 Technical data
Insulation coordination acc. to IEC 60664-1/IEC 60664-3 for the versions:
a)RCMS4x0-D1
Supply voltage U
S
.................................................................................DC 24…75 V/AC 24…60 V (AC/DC ±20 %)
Supply voltage frequency...........................................................................................................................DC, 50/60 Hz
Rated insulation voltage....................................................................................................................................... 100 V
Overvoltage category/pollution degree....................................................................................................................III/3
Rated impulse voltage......................................................................................................................................... 2.5 kV
Protective separation (reinforced insulation) between.................................. (A1, A2) - (k1, l…k12, R, T/R, T, A, B)
Voltage test acc. to IEC 61010-1 ......................................................................................................................1.344 kV
Rated insulation voltage....................................................................................................................................... 250 V
Overvoltage category/pollution degree....................................................................................................................III/3
Rated impulse voltage............................................................................................................................................. 4 kV
Basic insulation between:............................................................................... (A1, A2), (k1, l…k12, R, T/R, T, A, B) -
(C11, C12, C14), (C21, C22, C24), (11,14), (21,24), (31,34), (41,44), (51,54), (61,64), (71,74), (81,84),
(91,94),(101,104), (111,114), (121,124)
Basic insulation between: ............................................. (11, 14) - (21, 24) - (31, 34) - (41, 44) - (51, 54) - (61, 64)
Voltage test acc. to IEC 61010-1 ...................................................................................................................... 2.21 kV
Rated insulation voltage ....................................................................................................................................... 250 V
Overvoltage category/pollution degree....................................................................................................................III/3
Rated impulse voltage............................................................................................................................................. 6 kV
Protective separation (reinforced insulation) between.........................................(C11, C12, C14) - (C21, C22, C24) -
(11, 14, 21, 24, 31, 34) - (41, 44, 51, 54, 61, 64) - (71,74) - (81,84) - (91,94) - (101,104) - (111,114) - (121,124)
Voltage test acc. to IEC 61010-1 ...................................................................................................................... 3.536 kV

Table of Contents

Related product manuals