CT-600-2 81
Configuration parameters
No. Description Param. page
on HMI
Default
value
Default
unit
1 Nominal frequency Plant 1 50 Hz
2 System control voltage for CM Plant 1 230 V
3 Max capacity change Plant 1 5.0 %/s
4 Module capacity limiter step Plant 1 100.0 m3/h
5 Max no. of alarms in timespan window Plant 1 3
6 Alarm timespan window size Plant 1 300 s
7 Alarm auto-reset delay time Plant 1 30 s
8 Total current high warning Plant 1 10000 A
9 Total current high alarm Plant 1 11000 A
10 Remote process temp. sens. enable/disable Plant 1 ON
11 Suction pressure low alarm Plant 2 0.3 bara
12 Suction pressure low warning Plant 2 0.3 bara
13 Suction pressure high warning Plant 2 11.7 bara
14 Discharge pressure low warning Plant 2 1.5 bara
15 Discharge pressure low alarm Plant 2 1.5 bara
16 Discharge pressure high warning Plant 2 28.0 bara
17 Discharge pressure high alarm Plant 2 28.0 bara
18 Pressure ratio high warning Plant 2 50
19 Pressure ratio high alarm Plant 2 50
20 Pressure difference low alarm Plant 2 0.2 bar
21 Pressure difference low minimum value Tc 1 Plant 3 20 °C
22 Pressure difference low minimum value Tc 2 Plant 3 5 °C
23 Lubricating pressure low warning Plant 3 2.5 bar
24 Lubricating pressure low alarm Plant 3 1.0 bar
25 Suction superheat low warning Plant 3 0.0 °C
26 Suction superheat low alarm Plant 3 -100 °C
27 Suction superheat high warning Plant 3 20 °C
28 Suction superheat high alarm Plant 3 30 °C
29 Process temperature low warning Plant 3 3.0 °C
30 Process temperature low alarm Plant 3 0.5 °C
31 Pressure sensor HP low signal Plant 4 1.0 bara
32 Pressure sensor HP high signal Plant 4 26.0 bara
33 Pressure sensor LP low signal Plant 4 0.0 bara
34 Pressure sensor LP high signal Plant 4 10.0 bara
35 PT1000 temp. sensor low signal Plant 4 -40 °C