82 CT-600-2
No. Description Param. page
on HMI
Default
value
Default
unit
36 PT1000 temp. sensor high signal Plant 4 200 °C
37 NTC temp. sensor low signal Plant 4 5.2 °C
38 NTC temp. sensor high signal Plant 4 150 °C
39 Remote suc. press. sens. enable/disable Plant 4 ON
40 Remote suc. temp. sen. enable/disable Plant 4 ON
41 Remote disch. press. sens. enable/disable Plant 4 ON
42 Remote disch. temp. sen. enable/disable Plant 4 ON
43 Motor speed max VSD Comp./Motor 1 60 Hz
44 Motor speed min VSD Comp./Motor 1 25 Hz
45 CR step current limiter Comp./Motor 1 25 %
46 CR min before release VSD-regulation Comp./Motor 1 75 %
47 CR max high suction pressure limiter Comp./Motor 1 50 %
48 CR max low pressure difference limiter Comp./Motor 1 75 %
49 CR max for start-up Comp./Motor 1 25 %
50 CR min normal operation OS85 Comp./Motor 1 50 %
51 CR min normal operation OS95 Comp./Motor 1 25 %
52 CR max normal operation OS85 & OS95 Comp./Motor 1 100 %
53 Discharge temperature change high alarm (drop) Comp./Motor 2 -10 °C/s
54 Discharge superheat low warning Comp./Motor 2 15 °C
55 Discharge superheat low alarm Comp./Motor 2 10 °C
56 CM firmware version Release Comp./Motor 2 2
57 CM firmware version Version Comp./Motor 2 9
58 CM firmware version Level Comp./Motor 2 89
59 CM firmware version Patch Comp./Motor 2 0
60 Motor startup speed VSD Comp./Motor 2 35 Hz
61 Max motor speed change Comp./Motor 2 0.5 Hz/s
62 Motor error signal inversion Comp./Motor 2 low=error
63 Compressor 1, 2, 3 size & type Comp./Motor 3 -
1, 2, 3
UNKN.
64 Compressor 1, 2, 3 regulation type (CR/VSD) Comp./Motor 3 -
1, 2, 3
CR
65 Motor 1, 2, 3 current high warning Comp./Motor 3 -
1, 2, 3
0 A
66 Motor 1, 2, 3 current high alarm Comp./Motor 3 -
1, 2, 3
0 A