EasyManua.ls Logo

Bitzer ACP Link - Page 82

Bitzer ACP Link
109 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
82 CT-600-2
No. Description Param. page
on HMI
Default
value
Default
unit
36 PT1000 temp. sensor high signal Plant 4 200 °C
37 NTC temp. sensor low signal Plant 4 5.2 °C
38 NTC temp. sensor high signal Plant 4 150 °C
39 Remote suc. press. sens. enable/disable Plant 4 ON
40 Remote suc. temp. sen. enable/disable Plant 4 ON
41 Remote disch. press. sens. enable/disable Plant 4 ON
42 Remote disch. temp. sen. enable/disable Plant 4 ON
43 Motor speed max VSD Comp./Motor 1 60 Hz
44 Motor speed min VSD Comp./Motor 1 25 Hz
45 CR step current limiter Comp./Motor 1 25 %
46 CR min before release VSD-regulation Comp./Motor 1 75 %
47 CR max high suction pressure limiter Comp./Motor 1 50 %
48 CR max low pressure difference limiter Comp./Motor 1 75 %
49 CR max for start-up Comp./Motor 1 25 %
50 CR min normal operation OS85 Comp./Motor 1 50 %
51 CR min normal operation OS95 Comp./Motor 1 25 %
52 CR max normal operation OS85 & OS95 Comp./Motor 1 100 %
53 Discharge temperature change high alarm (drop) Comp./Motor 2 -10 °C/s
54 Discharge superheat low warning Comp./Motor 2 15 °C
55 Discharge superheat low alarm Comp./Motor 2 10 °C
56 CM firmware version Release Comp./Motor 2 2
57 CM firmware version Version Comp./Motor 2 9
58 CM firmware version Level Comp./Motor 2 89
59 CM firmware version Patch Comp./Motor 2 0
60 Motor startup speed VSD Comp./Motor 2 35 Hz
61 Max motor speed change Comp./Motor 2 0.5 Hz/s
62 Motor error signal inversion Comp./Motor 2 low=error
63 Compressor 1, 2, 3 size & type Comp./Motor 3 -
1, 2, 3
UNKN.
64 Compressor 1, 2, 3 regulation type (CR/VSD) Comp./Motor 3 -
1, 2, 3
CR
65 Motor 1, 2, 3 current high warning Comp./Motor 3 -
1, 2, 3
0 A
66 Motor 1, 2, 3 current high alarm Comp./Motor 3 -
1, 2, 3
0 A

Table of Contents