CT-600-2 87
Parameter Section User Setting
Minimum compressor capacity limit Config 25.00
Separate start signal from safety chain Config No
Compressor serial number (actual) CompInfo Number as on name plate
Customer, Location CompInfo Site description
System name, Compressor number CompInfo ACP type designation and compressor no.
on rack
Enable motor phase monitoring Phase Yes
Lowest allowed motor frequency Phase 20
Oil fault sensor type selection OilFault OS.A 85: FLOW
OS.A 95: LEVEL
Input ignore time during startup OilFault OS.A 85: 30
OS.A 95: 30
Delay time until fault is set OilFault OS.A 85: 5
OS.A 95: 0
Delay time until warning is set OilFault OS.A85: 5
OS.A95: 0
Enable oil fault protection – Input 2 OilFault2 OS.A85: Yes
OS.A95: No
Oil fault sensor2 type selection OilFault2 Pressure
Input2 ignore time during startup OilFault2 30
Delay time until fault is set – input 2 OilFault2 5
Delay time until warning is set – input 2 OilFault2 5
Enable application envelope protection Envelope No
Low pressure limit value PresLimit OSKA 85/95 Booster: 0.30
Select type of motor starter function MotorStart Direct On Line (DOL)
Start delay before oil filling OilInject 3
Enable stepped slider application StepSlider OS.A 85: Yes
OS.A 95: No
Enable position slider application SliderCtrl OS.A 85: No
OS.A 95: Yes
Compressor speed (frequency) at or
above which ECO valve can be opened
EcoValve 45
Compressor speed (frequency) below
which ECO valve shall be closed
EcoValve 70
Requested capacity at or above which
ECO valve can be opened at minimum VI
EcoValve OS.A85: 70
OS.A95: 95