88 CT-600-2
Parameter Section User Setting
Requested capacity at or above which
ECO valve can be opened at maximum
VI
EcoValve OS.A85: 70
OS.A95: 95
Requested capacity below which ECO
valve shall be closed at minimum VI
EcoValve OS.A85: 55
OS.A95: 90
Requested capacity below which ECO
valve shall be closed at maximum VI
EcoValve OS.A85: 55
OS.A95: 90
Actual capacity at or above which ECO
valve can be opened at minimum VI
EcoValve OS.A85: 75
OS.A95: 100
Actual capacity at or above which ECO
valve can be opened at maximum VI
EcoValve OS.A85: 75
OS.A95: 100
Actual capacity below which ECO valve
shall be closed at minimum VI
EcoValve OS.A85: 70
OS.A95: 98
Actual capacity below which ECO valve
shall be closed at maximum VI
EcoValve OS.A85: 70
OS.A95: 98
Serial Control Source SerCtrlCfg COM1 (MODBUS)
Serial Communication Timeout Function SerCtrlCfg Fault
Serial Communication Timeout SerCtrlCfg 15